Quadro de Cargas (QDAr1) - TÉRREO Circuito Descrição EsquemaMétodoTensão Tomadas (W) Pot. total.Pot. total.Fases Pot. - RPot. - SPot. - TFCTFCAIn'IpSeçãoIcIccDisjdV parc de inst.(V)815108516302200 (VA) (W) (W) (W) (W) (A)(A)(mm²)(A)(kA)(A) (%) 121Ar Condicionado EV - 19 F+F+T B1 220 V 1 1811 1630 R+S 815 815 1.000.7011.88.22.524.0510 1.72 122Ar Condicionado EV - 18 F+F+T B1 220 V 1 1206 1085 S+T 543 543 1.000.707.85.52.524.0510 0.69 123Ar Condicionado EV - 20 F+F+T B1 220 V 1 1206 1085 R+T 543 543 1.000.707.85.52.524.0510 0.81 124Ar Condicionado EV - 16 F+F+T B1 220 V 1 1811 1630 S+T 815 815 1.000.7011.88.22.524.0510 1.29 125Reserva F+F+T B1 220 V 0 0 R+S 1.001.000.00.02.524.0510 0.00 126Ar Condicionado EV - 17 F+F+T B1 220 V1 906 815 R+S 408 408 1.000.705.94.12.524.0510 0.61 127Motor CX-02 3F+T B1 220 V 1 3313 2200 R+S+T 733 733 733 1.000.7012.48.72.521.0510 0.94 128Motor EX-01 3F+T B1 220 V 1 3313 2200 R+S+T 733 733 733 1.000.7012.48.72.521.0510 0.90 129Reserva F+F+T B1 220 V 0 0 R+S 1.001.000.00.02.524.0510 0.00 TOTAL 1 2 2 2 13565 10645 R+S+T 3232 4047 3367 Quadro de Demanda (QDAr1) - TÉRREO Tipo de carga Potência instalada (kVA) Fator de demanda (%) Demanda (kVA) Condicionador de ar tipo janela (Não residencial)6.94 100.00 6.94 Motores 6.63 75.00 4.97 TOTAL 11.91 Quadro executivo - QDAr1 Trilho 1 13 24 B10 5 kA 13 24 B10 5 kA 13 24 B10 5 kA 13 24 B10 5 kA RESERVA Trilho 2 13 24 B10 5 kA 10 A - 5 kA - B10 A - 5 kA - B RESERVA NEUTRO 1 NEUTRO 2 TERRA 1 TERRA 2 Escala 1:5 R Branco S Preto T Vermelho N Azul PE Verde DPS 175 V - 8 kA QDAr1 Ar Condicionado EV - 19 121 1630 W 10 A Unipolar - PVC (70°C) 2.5 Ar Condicionado EV - 17126 815 W 10 A Unipolar - PVC (70°C) 2.5 Ar Condicionado EV - 18 122 1085 W 10 A Unipolar - PVC (70°C) 2.5 Motor CX-02127 2200 W 10 A Unipolar - PVC (70°C) 2.5 Ar Condicionado EV - 20 123 1085 W 10 A Unipolar - PVC (70°C) 2.5 Motor EX-01128 2200 W 10 A Unipolar - PVC (70°C) 2.5 Ar Condicionado EV - 16 124 1630 W 10 A Unipolar - PVC (70°C) 2.5 Reserva129 0 W 10 A Unipolar - PVC (70°C) 2.5 Reserva 125 0 W 10 A Unipolar - PVC (70°C) 2.5 Potência instalada (W) R 3232 S 4047 T 3367 Total 10645 Unipolar - PVC (70°C) 3#25(25)16mm² Conduto #100x75 70 A Verde QDG1 70 A 5 kA 25 16 R+S+T Unipolar - PVC (70°C) #100x75 70 A 5 kA DPS 4x175 V - 8 kA 10 A 5 kA 2.5 Unipolar - PVC (70°C) (1630 W) R+S 121 (Ar Condicionado EV - 19) 10 A 5 kA 2.5 Unipolar - PVC (70°C) (1085 W) S+T 122 (Ar Condicionado EV - 18) 10 A 5 kA 2.5 Unipolar - PVC (70°C) (1085 W) R+T 123 (Ar Condicionado EV - 20) 10 A 5 kA 2.5 Unipolar - PVC (70°C) (1630 W) S+T 124 (Ar Condicionado EV - 16) 10 A 5 kA 2.5 Unipolar - PVC (70°C) (0 W) R+S 125 (Reserva) 10 A 5 kA 2.5 Unipolar - PVC (70°C) (815 W) R+S 126 (Ar Condicionado EV - 17) 10 A 5 kA 2.5 Unipolar - PVC (70°C) (2200 W) R+S+T 127 (Motor CX-02) 10 A 5 kA 2.5 Unipolar - PVC (70°C) (2200 W) R+S+T 128 (Motor EX-01) 10 A 5 kA 2.5 Unipolar - PVC (70°C) (0 W) R+S 129 (Reserva) QDAr1 (10645 W) PLOTRAR COLORIDO NOTA 01 010203040506070809 010203040506070809 B C D E F G A B C D E F G A HH QUADROS DE CARGAS DO P AVIMENTO TÉRREO PROJETO ELÉTRICO CONTRATADO: INDICADAS NO DESENHO 10/13 CLIENTE: OBRA: Número Cliente: EST ESCALA: DESENHO NÚMERO: MOD: FOLHA: VERIFPRO APROV DATA NOME REVIS. PROJETO: 00001 REFERÊNCIA: (1°DIEDRO)UNIDADE: (EXCETO INDICADO) cm REVISÃO: 00 TÍTULO: 10 ELE CREA: JÚLIA VILELA DE FARIA 86/2024 18/11/2024 MINISTÉRIO DA SAÚDE UBS 4 SECRETARIA DE ATENÇÃO ESPECIALIZADA A SAÚDE CREA/MG - 313914/D 18/11/2024