Quadro de Cargas (QDAr4) - TÉRREO Circuito Descrição EsquemaMétodoTensão Tomadas (W) Pot. total.Pot. total.Fases Pot. - RPot. - SPot. - TFCTFCAIn'IpSeçãoIcIccDisjdV parc de inst.(V)815150016303500 (VA) (W) (W) (W) (W) (A)(A)(mm²)(A)(kA)(A) (%) 158Ar Condicionado EV - 06 F+F+T B1 220 V 1 3889 3500 R+T 1750 1750 1.000.7224.617.7432.0520 1.59 159Ar Condicionado EV - 04 F+F+T B1 220 V1 906 815 S+T 408 408 1.000.725.74.12.524.0510 0.41 160Ar Condicionado EV - 03 F+F+T B1 220 V1 906 815 R+S 408 408 1.000.725.74.12.524.0510 0.49 161Ar Condicionado EV - 05 F+F+T B1 220 V1 906 815 S+T 408 408 1.000.725.74.12.524.0510 0.47 162Reserva F+F+T B1 220 V 0 0 R+S 1.001.000.00.02.524.0510 0.00 163Ar Condicionado EV - 01 F+F+T B1 220 V 1 3889 3500 R+S 1750 1750 1.000.7025.317.7432.0520 1.36 164Ar Condicionado EV - 02 F+F+T B1 220 V 1 3889 3500 S+T 1750 1750 1.000.7025.317.7432.0520 1.35 165Ar Condicionado EV - 07 F+F+T B1 220 V 1 1811 1630 R+T 815 815 1.000.7011.88.22.524.0510 1.44 166Motor - CX03 3F+T B1 220 V 1 2331 1500 R+S+T 500 500 500 1.000.708.76.12.521.0510 0.56 167Reserva F+F+T B1 220 V 0 0 R+S 1.001.000.00.02.524.0510 0.00 TOTAL 3 1 1 3 18525 16075 R+S+T 5223 5223 5630 Quadro de Demanda (QDAr4) - TÉRREO Tipo de carga Potência instalada (kVA) Fator de demanda (%) Demanda (kVA) Condicionador de ar tipo janela (Não residencial)16.19 100.00 16.19 Iluminação e TUG's (Clínicas e hospitais) 2.33 40.00 0.93 TOTAL 17.13 Quadro executivo - QDAr4 Trilho 1 13 24 B10 5 kA 13 24 B10 5 kA 13 24 B10 5 kA 13 24 B20 5 kA RESERVA Trilho 2 13 24 B20 5 kA 13 24 B20 5 kA 13 24 B10 5 kA 10 A - 5 kA - B RESERVA NEUTRO 1 NEUTRO 2 TERRA 1 TERRA 2 Escala 1:5 R Branco S Preto T Vermelho N Azul PE Verde DPS 175 V - 8 kA QDAr4 Ar Condicionado EV - 06 158 3500 W 20 A Unipolar - PVC (70°C) 4 Ar Condicionado EV - 01163 3500 W 20 A Unipolar - PVC (70°C) 4 Ar Condicionado EV - 04 159 815 W 10 A Unipolar - PVC (70°C) 2.5 Ar Condicionado EV - 02164 3500 W 20 A Unipolar - PVC (70°C) 4 Ar Condicionado EV - 03 160 815 W 10 A Unipolar - PVC (70°C) 2.5 Ar Condicionado EV - 07165 1630 W 10 A Unipolar - PVC (70°C) 2.5 Ar Condicionado EV - 05 161 815 W 10 A Unipolar - PVC (70°C) 2.5 Motor - CX03166 1500 W 10 A Unipolar - PVC (70°C) 2.5 Reserva 162 0 W 10 A Unipolar - PVC (70°C) 2.5 Reserva167 0 W 10 A Unipolar - PVC (70°C) 2.5 Potência instalada (W) R 5223 S 5223 T 5630 Total 16075 Unipolar - PVC (70°C) 3#16(16)16mm² Conduto #100x75 63 A Verde QDG1 63 A 5 kA 16 R+S+T Unipolar - PVC (70°C) #100x75 63 A 5 kA DPS 4x175 V - 8 kA 20 A 5 kA 4 Unipolar - PVC (70°C) (3500 W) R+T 158 (Ar Condicionado EV - 06) 10 A 5 kA 2.5 Unipolar - PVC (70°C) (815 W) S+T 159 (Ar Condicionado EV - 04) 10 A 5 kA 2.5 Unipolar - PVC (70°C) (815 W) R+S 160 (Ar Condicionado EV - 03) 10 A 5 kA 2.5 Unipolar - PVC (70°C) (815 W) S+T 161 (Ar Condicionado EV - 05) 10 A 5 kA 2.5 Unipolar - PVC (70°C) (0 W) R+S 162 (Reserva) 20 A 5 kA 4 Unipolar - PVC (70°C) (3500 W) R+S 163 (Ar Condicionado EV - 01) 20 A 5 kA 4 Unipolar - PVC (70°C) (3500 W) S+T 164 (Ar Condicionado EV - 02) 10 A 5 kA 2.5 Unipolar - PVC (70°C) (1630 W) R+T 165 (Ar Condicionado EV - 07) 10 A 5 kA 2.5 Unipolar - PVC (70°C) (1500 W) R+S+T 166 (Motor - CX03) 10 A 5 kA 2.5 Unipolar - PVC (70°C) (0 W) R+S 167 (Reserva) QDAr4 (16075 W) PLOTRAR COLORIDO NOTA 01 010203040506070809 010203040506070809 B C D E F G A B C D E F G A HH QUADROS DE CARGAS DO P AVIMENTO TÉRREO PROJETO ELÉTRICO CONTRATADO: INDICADAS NO DESENHO 13/13 CLIENTE: OBRA: Número Cliente: EST ESCALA: DESENHO NÚMERO: MOD: FOLHA: VERIFPRO APROV DATA NOME REVIS. PROJETO: 00001 REFERÊNCIA: (1°DIEDRO)UNIDADE: (EXCETO INDICADO) cm REVISÃO: 00 TÍTULO: 13 ELE CREA: JÚLIA VILELA DE FARIA 86/2024 18/11/2024 MINISTÉRIO DA SAÚDE UBS 4 SECRETARIA DE ATENÇÃO ESPECIALIZADA A SAÚDE CREA/MG - 313914/D 18/11/2024